Adding more biocide is a common response to slime, but biocide reaches microbes inside a surface film poorly. What actually feeds slime can be established biofilm, low biocide residual, a single biocide routine, nutrient ingress or stagnant zones, and several of these can act together.
Sometimes a slippery brown or grey film builds up on the basin walls and fill of a cooling tower, and sticky clumps gather round the distribution nozzles. A dose of biocide seems to shrink it for a while, then it returns, and someone mentions that the process side leaves the heat exchanger warmer than before at the same load. Slime comes less from bacteria floating in the water than from microbial film growing on surfaces, so growth can carry on at the surfaces while the water looks clear.
Slime harms heat transfer, equipment and safety together. Even a thin film inside heat exchanger tubes adds thermal resistance and cuts cooling performance, and its rough surface raises flow resistance (Characklis et al., 1981). Under the film, microbial metabolism can cause local corrosion of the metal, known as microbiologically influenced corrosion, or MIC (Little & Lee, 2007). Safety weighs heaviest. Legionella is a waterborne bacterium that causes Legionnaires' disease, a severe pneumonia, and Pontiac fever, a mild flu-like illness; it multiplies inside protozoa such as amoebae (Fields et al., 2002) and uses biofilm as a refuge from disinfection (Abdel-Nour et al., 2013). A cooling tower mixes air and water and releases fine droplets, so Legionella that grows in the cooling water can reach people nearby (CDC, n.d.; HSE, 2024).
An open cooling tower rejects heat by evaporating water. Air and water meet over a large area, the water is warm and evaporation concentrates what is dissolved in it, so microbes grow well there. They attach to surfaces and build a film called biofilm, and biofilm that grows past a manageable level and causes problems is called biofouling (Flemming, 2002). The sticky matrix of the film shields the cells inside from biocide and drying (Flemming & Wingender, 2010), so counts in the water alone do not tell the whole story of slime. Legionella multiplies at 20 to 45°C when nutrients are present, lies dormant below 20°C and does not survive above 60°C (HSE, n.d.), and cooling water usually sits inside that growth range.
In such cases the technical team sets up the five hypotheses below and rules them out one by one. The start is always the same: measure the free chlorine residual of the circulating water, or the residual of whatever biocide is in use, at the same time as pH, compare both with the targets in the treatment plan, and rub the fill and basin wall by hand to feel for slime.
Hypothesis 1: established biofilm
When the water is clear but surfaces feel slippery, start with this hypothesis. Look for it in towers cleaned at long intervals, deep inside fill packs that are hard to reach, on slow-flow surfaces such as nozzles and basin corners, and in summer when the water warms. Pull one fill sheet during a shutdown and it looks fine on the outside, yet a finger run along the grooves comes away streaked with brown film. A circulating water sample taken the same day reads a low count.
Bacteria that reach a surface attach where they land and release polymers such as polysaccharides, proteins and nucleic acids. This material binds the cells together and fixes them to the surface as a sticky matrix, and it is the slime you see. The matrix holds enzymes near the cells, so it works like an external digestive system for organic matter in the water, and it shields the cells inside from biocide and drying (Flemming & Wingender, 2010). That is why a biocide dose that works well on floating bacteria works far less well on bacteria inside the film (Bridier et al., 2011).
The harm to heat transfer and metal comes from the same structure. The film is mostly water and conducts heat far worse than metal, so even a thin layer on a tube wall adds measurable thermal resistance (Characklis et al., 1981). As the film thickens, its inner layers run short of oxygen, and microbes there, such as sulfate-reducing bacteria, can produce corrosive products that pit the metal underneath (Little & Lee, 2007).
The quickest check is by hand. If rubbing the fill, basin wall or nozzles leaves a slippery feel or a brown or grey film, biofilm is present. Water counts can be low while surfaces carry film, so swab the surfaces alongside the water samples and test both by the same method. Measuring ATP, an energy molecule found only in living cells, gives a fast reading of microbial activity (ASTM International, 2023). If the heat exchanger's inlet-to-outlet temperature difference slowly shrinks at the same load, suspect film inside the tubes (Characklis et al., 1981).
Where film is widespread, cleaning comes before biocide. Established biofilm does not come off well with biocide alone, so combine mechanical cleaning with a biodispersant, a surfactant that loosens the film, before disinfecting (Flemming, 2002; HSE, 2024). After cleaning, record surface samples and ATP as a baseline and re-measure the same points on a fixed schedule. When heat exchanger performance starts to fall below that baseline, take it as a signal to step up treatment, even before slime is visible.
Hypothesis 2: low biocide residual
If microbes keep coming back although biocide goes in at the same dose every time, suspect the residual, the amount of biocide actually left in the water. It tends to happen in towers that run at high pH as the water concentrates, in systems open to process contamination, and on sites where dosing pumps often stop or chemical tanks run dry. In some systems a sample taken right beside the dosing point shows plenty of residual, while one from the far side of the basin or a distant exchanger outlet shows almost none. Move the sampling time to just before the next dose and the gap widens further.
A chlorine biocide splits into two forms in water: hypochlorous acid, HOCl, which is the stronger killer, and the weaker hypochlorite ion, OCl⁻. The ion's share grows as pH rises (EPA, 1999), so the same chlorine reading can mean less real kill in high-pH water. The UK Health and Safety Executive's guidance on cooling systems treats the effect of cooling water pH on chlorine and bromine biocides as a topic of its own (HSE, 2024).
pH is not the only thing eating into the residual. Oxidising biocides react not only with microbes but with organic matter, ammonia and reducing substances in the water, and are used up (EPA, 1999), so when process leaks or contamination increase, the same dose leaves no residual. A literature review finds oxidising biocides generally more effective against Legionella than non-oxidising ones (Kim et al., 2002), but that holds only while a residual is kept.
Measure the residual on site with the DPD reagent method (HSE, 2024). One reading right after dosing, one just before the next dose and one far from the dosing point show when and where the residual is lost, and pH logged at the same moments shows how much that number is really worth. If a higher dose does not lift the residual, something is consuming more biocide, so look for the contamination source. Keep the dosing pump run log and tank levels in the same table.
Once low residual shows up, write target residual and pH ranges into the treatment plan as numbers, based on the treatment provider's advice and applicable guidance (ASHRAE, 2021; HSE, 2024). In a system run at high pH, review with the provider a switch to an oxidiser less affected by pH, or a change in pH control. Check dosing pumps and tank levels daily so dosing never stops, and when the residual drops suddenly, find what is consuming it before raising the dose.
Hypothesis 3: one biocide routine
Consider this hypothesis when counts fall sharply after each treatment but soon return, again and again. It appears in systems that have used the same product at the same dose and interval for a long time, in programmes that rely on one oxidiser alone, and where blowdown, the discharge of concentrated water, stays open right after dosing. Open the log of a tower dosed with the same product on the same day each month, and ATP drops low the day after dosing, then climbs back to where it started well before the next dose is due.
Several reasons combine to let biofilm withstand biocide. The matrix reacts with the biocide first and limits how much reaches the inside, inner cells grow slowly on little nutrient and oxygen and become less sensitive, and some cells shift into a stress-tolerant state (Bridier et al., 2011). Using the same product at the same dose and timing every time trims only the outer layer, and the surviving inner cells grow back to fill the film.
Non-oxidising biocides are used to cover microbes and biofilm that oxidisers handle poorly. Each product works on a different range of microbes, though, and needs enough contact time to act. The US Occupational Safety and Health Administration notes that quaternary ammonium compounds, widely used against biofouling in cooling towers, may not fully control Legionella (OSHA, n.d.).
Recovery speed gives this hypothesis away. Run ATP or culture tests at the same point just before a treatment, just after it and just before the next, and see how fast the counts come back (ASTM International, 2023). Log dosing and blowdown times as well. If blowdown was open right after dosing, some of the product may have left before its contact time was met.
On top of a constant oxidiser residual, plan with the treatment provider a periodic slug dose, one large single addition, of a non-oxidising biocide with a different mode of action. Close blowdown during the slug dose to keep the contact time, and follow the dose and time on the product label and safety data sheet, the SDS. If recovery keeps getting faster, shorten the interval or add a biodispersant.
Hypothesis 4: nutrient ingress
If treatment has not changed but slime has started to spread fast, look at whether the microbes are getting more food. Plants where cooling water serves exchangers carrying process fluid are prone to it, as are towers sited in dusty or pollen-heavy surroundings and units where sunlight falls straight onto the basin and distribution decks. Take a plant where one tube in an old exchanger has a pinhole and process liquid seeps slowly into the cooling water. A faint oil sheen shows on the basin, the odour changes, and the chlorine residual vanishes faster than before at the same dose.
Nutrient that enters cooling water can turn into microbial biomass. The more dissolved organic matter, the more and the faster biofilm builds (Flemming, 2002). Nutrient arrives by three routes: process material such as oil, sugars and alcohols through exchanger leaks, dust and pollen drawn in from the air, and the make-up water itself. A tower concentrates its water by evaporation, so even a little nutrient in the make-up water becomes several times stronger in the circulating water.
It is easy to assume that cutting phosphorus will slow growth. In pilot cooling towers, however, limiting phosphate did not prevent biofilm, and the film that formed held more organic matter per unit of active biomass (Pinel et al., 2020). Closing off the routes works better than cutting a single nutrient. Where sunlight reaches the basin and fill, algae grow and feed other microbes, so HSE guidance advises shading them from light (HSE, 2024).
Begin by asking whether biocide demand has jumped. If an oil sheen, odour or colour change comes with it, suspect a process leak first. Measure organics in the circulating and make-up water together as total organic carbon, TOC, or chemical oxygen demand, COD. The number of times stronger the circulating water is than the make-up is called the concentration ratio, and if the circulating value exceeds the make-up value multiplied by that ratio, organics are entering by some route other than the make-up. Isolating exchangers one at a time and sampling each outlet narrows down the leak, and a green film on basin walls or distribution decks points to algae.
A leaking exchanger should be repaired rather than outlasted with more biocide. Until the repair, measure residual and counts more often and raise blowdown to lower the concentration. In dusty surroundings, use side-stream filtration, which continuously filters part of the circulating water, to remove suspended solids, and cover the basin and decks to keep sunlight out (ASHRAE, 2021; HSE, 2024).
Hypothesis 5: stagnant zones
When residual and counts in the main loop look fine but slime keeps coming back, search for places where water hardly moves. Typical ones are dead legs, which are closed-off branches, standby pumps and exchangers run in turn, idle cells in a multi-cell tower, bypass lines and sediment in basin corners. A plant with a standby exchanger used only in the summer peak can see this: within days of opening the valves on an exchanger that sat for months, counts across the whole system jump and flakes of slime float in the basin.
Biocide travels with flowing water. Where water barely moves no fresh biocide arrives, so the residual there is soon used up, the water stays warm and settled sediment becomes food and shelter. The US Centers for Disease Control and Prevention names sediment and biofilm, temperature, water age and disinfectant residual as key factors in Legionella growth in cooling towers (CDC, n.d.). Film grown in stagnant zones breaks off when flow changes and reseeds the whole system.
The work starts with marking such places on the system drawing. Measure residual and counts at each mark and set them beside the main-loop values, and the spots biocide never reaches show up as numbers. If counts across the system spike right after standby equipment starts, microbes grown in a stagnant zone have most likely been released. Note where sediment has gathered in the basin and how much.
Remove unused branches where possible. Flush the low-flow lines and dead legs that must stay every week, as CDC advises (CDC, n.d.). Spread run time evenly across cells or towers, and clean and disinfect equipment that has stood idle for a long time before it goes back into service (ASHRAE, 2021; CDC, n.d.). Put basin sediment on the routine cleaning schedule and keep cleaning records with the treatment log.
Testing the hypotheses
Order the work by how little effort each measurement takes. The first step is residual and pH. Measure both right after dosing, just before the next dose and at a remote point; if the residual is below target or pH runs high, put hypothesis 2 first (EPA, 1999; HSE, 2024). On the same day, rub the fill and basin and take surface samples. Clean water over slimy surfaces means hypothesis 1.
Next comes how things move over time. Set ATP from just before a treatment, just after it and just before the next side by side; a fast rebound after treatment points to hypothesis 3 (ASTM International, 2023; Bridier et al., 2011). If biocide demand has risen and TOC or COD, oil sheen and odour have worsened together, look towards hypothesis 4 and an exchanger leak (Flemming, 2002). If the main loop is fine but counts spike after standby equipment runs, or values at the marked points differ widely from the main loop, look at hypothesis 5 (CDC, n.d.).
If that still does not settle it, run a control comparison within the same system. Measure near and far from the dosing point, equipment that always runs against equipment that sat idle, and the outlet of a suspect exchanger against another exchanger's outlet, on the same day by the same method; where the values split widely is where to look for the cause. Take surface samples in the same pairs.
The final check is a Legionella test. Total counts and ATP cannot show Legionella, so test for it separately, and if any check above fails, send a sample outside the routine schedule. Culture testing usually goes to a laboratory following the ISO 11731 method, and results come as colony-forming units per mL, CFU/mL (ISO, 2017). CDC treats 10 CFU/mL or more in a cooling tower as a signal to recheck control, and adds that no Legionella level is known to be safe (CDC, n.d.). After corrective action, retest for Legionella, and judge the job done only when residual, ATP and surface samples stay within limits over several checks in a row.
The hypotheses can also appear tangled together. Nutrient-rich water eats into the residual quickly, and film grown in stagnant zones reseeds the main loop. When several signs show at once, first shut off the causes that keep supplying microbes, such as nutrient ingress and stagnant zones, then remove biofilm by mechanical cleaning and rebuild the biocide plan. Changing only the biocide while film remains makes it hard to judge what worked.
Limits and cautions
Control limits and test frequency vary with national and local law and with the equipment, so take figures from the applicable guidance and the treatment plan set by the provider, and read the quoted figures as those of each cited body. Closed cooling loops, large once-through systems such as power plants, and water for food or pharmaceutical processes have their own limits and regulations, apart from open towers. Legionella culture tests miss bacteria in a non-culturable state (ISO, 2017), so do not conclude there is no risk from a single negative result.
Many biocides and dispersants harm skin, eyes and lungs. Read the SDS before dosing or sampling, and wear safety glasses, chemical-resistant gloves and, where needed, respiratory protection. Never mix an oxidiser with other chemicals in one container. A water management programme for each tower, documenting hazard points, control limits, measurement frequency, corrective actions and who is responsible, is the core of ASHRAE Standard 188 and CDC guidance (ASHRAE, 2021; CDC, n.d.).
If people working near a tower show pneumonia or flu-like symptoms, or a Legionella result is far above the limit, do not settle it on floor judgement; follow water treatment specialists and public health procedures. Leave work that exposes people to fine droplets, such as cleaning inside the tower, to specialist contractors (HSE, 2024; OSHA, n.d.).
Sources
- Abdel-Nour, M., Duncan, C., Low, D. E., & Guyard, C. (2013). Biofilms: The stronghold of Legionella pneumophila. International Journal of Molecular Sciences, 14(11), 21660–21675. https://doi.org/10.3390/ijms141121660
- ASHRAE. (2021). ANSI/ASHRAE Standard 188-2021, Legionellosis: Risk management for building water systems. https://www.ashrae.org/technical-resources/standards-and-guidelines/guidance-for-water-system-risk-management
- ASTM International. (2023). ASTM D4012-23a, Standard test method for adenosine triphosphate (ATP) content of microorganisms in water. https://store.astm.org/d4012-23a.html
- Bridier, A., Briandet, R., Thomas, V., & Dubois-Brissonnet, F. (2011). Resistance of bacterial biofilms to disinfectants: A review. Biofouling, 27, 1017–1032.
- Centers for Disease Control and Prevention [CDC]. (n.d.). Legionella control toolkit: Controlling Legionella in cooling towers; Routine testing for Legionella. https://www.cdc.gov/control-legionella/php/toolkit/cooling-towers-module.html, https://www.cdc.gov/control-legionella/php/toolkit/routine-testing-module.html
- Characklis, W. G., Nimmons, M. J., & Picologlou, B. F. (1981). Influence of fouling biofilms on heat transfer. Heat Transfer Engineering, 3(1), 23–37. https://doi.org/10.1080/01457638108939572
- Fields, B. S., Benson, R. F., & Besser, R. E. (2002). Legionella and Legionnaires' disease: 25 years of investigation. Clinical Microbiology Reviews, 15(3), 506–526. https://doi.org/10.1128/CMR.15.3.506-526.2002
- Flemming, H.-C. (2002). Biofouling in water systems: Cases, causes and countermeasures. Applied Microbiology and Biotechnology, 59, 629–640. https://doi.org/10.1007/s00253-002-1066-9
- Flemming, H.-C., & Wingender, J. (2010). The biofilm matrix. Nature Reviews Microbiology, 8, 623–633. https://doi.org/10.1038/nrmicro2415
- Health and Safety Executive [HSE]. (2024). HSG274 Legionnaires' disease: Technical guidance. Part 1: The control of legionella bacteria in evaporative cooling systems (2nd ed.). https://www.hse.gov.uk/pubns/books/hsg274.htm
- Health and Safety Executive [HSE]. (n.d.). Managing legionella in hot and cold water systems. https://www.hse.gov.uk/healthservices/legionella.htm
- International Organization for Standardization [ISO]. (2017). ISO 11731:2017, Water quality: Enumeration of Legionella. https://www.iso.org/standard/61782.html
- Kim, B. R., Anderson, J. E., Mueller, S. A., Gaines, W. A., & Kendall, A. M. (2002). Literature review: Efficacy of various disinfectants against Legionella in water systems. Water Research, 36(18), 4433–4444. https://doi.org/10.1016/S0043-1354(02)00188-4
- Little, B. J., & Lee, J. S. (2007). Microbiologically influenced corrosion. Wiley-Interscience.
- Occupational Safety and Health Administration [OSHA]. (n.d.). Legionellosis: Control and prevention; OSHA technical manual, chapter on Legionnaires' disease. U.S. Department of Labor. https://www.osha.gov/legionnaires-disease/control-prevention
- Pinel, I. S. M., et al. (2020). Effect of phosphate availability on biofilm formation in cooling towers. Biofouling, 36(7), 800–815. https://doi.org/10.1080/08927014.2020.1815011
- U.S. Environmental Protection Agency [EPA]. (1999). Alternative disinfectants and oxidants guidance manual (EPA 815-R-99-014). https://www.usbr.gov/lc/region/programs/quagga/docs/EPAGuidanceManual.pdf