Why predictive maintenance AI stalls on rare failures

Type
Kaltec Voices
Published
24 November 2026
Prepared by
Byunghoon So
Role
ML / AI Engineer

Predictive maintenance AI catches drift from the record of normal running, but the causes of seal and bearing failures that come a few times a year are not in the sensor data. What teaches a model about rare failures is the cause record written by the person who took the machine apart, with the symptom and cause, how and by whom it was confirmed, and how far the alarm was from the event.

Background

It was an afternoon walk on the equipment round. The maintenance foreman ahead of me stopped in front of a process water transfer pump. Under the low hum of the motor there was a thin, sharp squeal. He put his listening rod on the seal housing and said the seal sounded different from usual, and when he bent down there were drops of water forming under the gland. On my tablet's predictive maintenance screen, that pump was green. The model stayed quiet until the end of the day.

When a model that alarms readily on common anomalies goes quiet in front of an expensive failure, the first response is usually to collect more data or use a bigger model. I think the reason a model stalls on rare failures lies in its material more than in its math. Rare failures can only be learned from the cause records people write after confirming a failure, not from sensor data.

The arithmetic that shakes alarms on rare failures

A plant may have dozens of centrifugal pumps, yet only a few have a mechanical seal fail in a year. As training data, that is tens of thousands of rows of normal running and a handful of rows before a failure. Split by cause, it gets thinner. If a seal that ran dry because its flush was blocked, a seal whose shaft shook from running far from the best efficiency point and a seal whose face material did not suit the liquid each come to one or two cases, the model has practically no examples to learn the shape of each cause. So predictive maintenance on site usually becomes anomaly detection, which learns only normal running and reports drift. Anomaly detection can say something is different, but it cannot say it is the seal.

With rare events, alarm precision shakes too. When the event you are looking for is rare, the chance that a raised alarm is right depends on the false alarm rate, and unless that rate is pushed very low, most alarms that sound are false. Intrusion detection research called this the base-rate fallacy (Axelsson, 2000). Let me work it out for pumps. Judging 100 pumps once a day gives 36,500 judgments a year. Say 50 of those days show an early sign of failure, and the model catches 90% of them while sounding wrongly on only 1% of normal days. That is 45 correct alarms and about 365 false ones. Of 410 alarms, a little over one in ten is right. On a performance sheet, this model reads as 90% recall and a 1% false alarm rate. If those 50 days are the lead-up to a few seal failures, recall counted per failure is yet another number.

When nine alarms in ten are false, the maintenance team asks for a higher threshold, and a higher threshold misses the weak early signs of rare failures first. That pump had a history of exactly that kind of adjustment.

Alarms come from symptoms, causes sit outside the sensors

A few days later we took the seal apart and found that the orifice in the flush line was blocked and the seal faces had been running dry. The model was quiet because of distance. The sensors on that pump measured vibration and temperature at the bearing housing. When a seal starts to run dry, the first things to change are the seal face temperature, the pressure and temperature in the flush line, the leakage at the gland and the sound the foreman heard. Bearing vibration moves only after the seal is badly damaged and leaking liquid has reached the bearing side. When the place you measure is far from the place that fails, the alarm comes late or not at all, however refined the model is.

Maintenance has a term for this distance. The time between the point when a failure's early sign can first be noticed and the point when the function is lost is called the P-F interval, and it differs by failure mode and by what you watch it with (Moubray, 1997). A seal that loses its flush fails as its faces are damaged by heat within a short time, so the interval is short, and seen through bearing vibration almost none of it is left.

Under-lubricated blower bearings are the opposite shape. When grease starts to run short, fine metal-to-metal friction rises first in the high-frequency bands and in ultrasound. The overall vibration velocity rises only after the raceway starts to be damaged, and bearing temperature later still. The interval is long, but a sensor that takes only the overall value and temperature cannot see its front end. On blowers like that, the day the model raised an alarm was already the day the bearing had to be replaced, and the alarm said nothing about grease running short. An alarm sounds where the symptom reaches a measured value, and the cause sits ahead of it, usually outside the sensors. Adding sensors works only when you know where to put them, and the record of a confirmed cause tells you where.

The cause labels public failure data lacks

When cases run short, the first thought is to fill the gap with public data. The Case Western Reserve University data, the most used in bearing diagnostics research, are signals from bearings run on a test rig after their inner race, outer race or balls were deliberately notched by electrical discharge machining. A study that diagnosed the whole data set again with benchmark methods found that diagnostic difficulty varied widely by record. It also pointed out problems in the data itself (Smith and Randall, 2015). The test rig at the FEMTO-ST institute in France does not notch the bearings. Instead it applies a radial load above the maximum dynamic load the bearing can carry and degrades it to the end within a few hours (Nectoux et al., 2012).

In the first data set people made the damage, so we know where it is. In the second, we know when the bearing ended. Both labels tell only where the damage is or how much life is left, not why it happened, because load, rotating speed and lubrication are conditions the rig sets in advance. Causes on site are different. Grease after a skipped regreasing, dust inside the housing and load from an overtightened belt pile up on one bearing. For mechanical seals, public data is rare in the first place. A model trained on public data can say outer race defect, but it cannot say this blower had a long regreasing interval.

Records inside the plant are in a similar state. Maintenance work orders hold a machine's history, but they are written in short free text and abbreviations, and researchers have pointed out that general natural language processing cannot read them as they are (Brundage et al., 2021). In the pump maintenance records I have received, too, many rows had an action such as seal replaced or leak fixed where the cause should be. An action tells you what was done, not why the next seal will fail.

Putting it to work

When a rare failure is closed, leave one cause record. Filled in for that day's pump seal, it looks like this.

In the Symptom field, write who noticed first and with what. The foreman's ear, a squeal at the seal housing, leakage at the gland. The fact that a human sense caught it before a sensor shows the gap in your measurement list. In the Confirmed cause field, write why it failed. For this seal, the flush orifice was blocked and the seal ran dry.

In the How confirmed field, write whether you took the seal apart and looked at the faces, or cleared the flush line. A seal that ran dry leaves heat cracks and discoloration on its faces, so attaching one photo of the faces lets someone else judge the cause again later. A row confirmed by teardown and a row written from a guess should carry different weight in training, and without this field you cannot tell them apart. The Confirmed by field gives you someone to ask when the same symptom comes back, and lets you rate how far to trust each label.

The last field is Time from alarm. Write whether the model sounded days before a person noticed, sounded later or did not sound at all. The most valuable rows are the ones that say no alarm. They are the only place that counts the failures the model missed, and the material for measuring the recall on the performance sheet again on site. In the other direction, when an alarm sounded and the machine was fine when opened, record the value that triggered it and what you found in one row, and you will see which measurements those 365 false alarms came from. If you have brought in predictive maintenance or plan to, how many of these rows pile up in a year comes before the model's accuracy table. What the model can learn about rare failures cannot exceed that number of rows.

Conclusion

In one plant, only a few cause rows for seal and bearing failures appear each year. Someone who has supplied bearing grease and lubricants to pumps and blowers across many plants, and left a cause row at every teardown, sees those rows as many times over as there are plants. There, the same types of bearings and seals are seen failing from the same causes again and again, and blower bearings damaged by a long regreasing interval are one of them. Each plant's records stay separate, and what builds up is an engineer's order of what to open first for a given symptom.

As rows of confirmed causes and rows of opened false alarms pile up, you can see which measurement moved first for each cause, and set thresholds again cause by cause. False alarms will drop first on the machines where those rows have piled up. What the model learns, and what the engineer decides to open first, both start from those rows.

One rare failure, five fields, one person who confirmed it.

Sources

  • Axelsson, S. (2000). The base-rate fallacy and the difficulty of intrusion detection. ACM Transactions on Information and System Security, 3(3), 186-205.
  • Brundage, M. P., Sexton, T., Hodkiewicz, M., Dima, A., Lukens, S. (2021). Technical language processing: Unlocking maintenance knowledge. Manufacturing Letters, 27, 42-46. https://doi.org/10.1016/j.mfglet.2020.11.001
  • Moubray, J. (1997). Reliability-centred maintenance, 2nd ed. Butterworth-Heinemann.
  • Nectoux, P., Gouriveau, R., Medjaher, K., Ramasso, E., Chebel-Morello, B., Zerhouni, N., Varnier, C. (2012). PRONOSTIA: An experimental platform for bearings accelerated degradation tests. IEEE International Conference on Prognostics and Health Management, Denver. https://hal.archives-ouvertes.fr/hal-00719503/
  • Smith, W. A., Randall, R. B. (2015). Rolling element bearing diagnostics using the Case Western Reserve University data: A benchmark study. Mechanical Systems and Signal Processing, 64-65, 100-131. https://doi.org/10.1016/j.ymssp.2015.04.021

Product and site consultation

Leave your company, site and the product groups in use. Our engineer will get in touch to go through your site conditions and concerns. Materials, equipment, operating conditions and downstream steps show what should change and what can stay. If nothing needs to change, we will say so.

Contact us
After you contact us
  1. 01
    Site setup

    We confirm process conditions and needs first.

  2. 02
    Spec design

    We set the product spec and selection criteria.

  3. 03
    Comparison

    We compare matching candidates and propose.

  4. 04
    Tailored supply

    We supply on time and manage the stock.

  5. 05
    Site check

    We visit, check conditions of use and record.

  6. 06
    Use management

    We track use and change cycles to catch issues.

  7. 07
    Regular analysis

    We analyze the records and send a yearly report.