Why do contact cleaners leave faults and leakage current behind?

Type
Application notes
Published
23 November 2026
Prepared by
Jonghwan Moon
Product group
Cleaning & Surface Prep

Spraying again to wash the problem away is the usual response when faults follow a contact cleaner, but if the cause is moisture or residue the cleaner left behind, or a part it damaged, more spray can make things worse. What actually lies behind it can be condensation from evaporative chilling, contamination that dissolved and settled again, power-up while still wet, plastics damaged by solvent or a cleaner that leaves a film, and sometimes two or more at once.

Background

A terminal block or relay contact in a control panel plays up, so it gets a spray of contact cleaner, but at power-up the signal starts dropping in and out and the residual current breaker trips. A fault that was in one place before spraying can spread to several, or the panel runs fine for a day or two and the fault returns on a humid day. The equipment stops again, and with the cause unknown, sound parts get replaced or the same cleaner is sprayed again. Power applied while things are still wet can do more than damage equipment; it can lead to sparks and burns.

A contact cleaner is a volatile solvent made to dissolve oil, dust and flux residue and then evaporate away itself, usually packed in a can with a propellant. The resistance of a contact is the sum of the resistance created as current crowds into the small spots that actually touch and the resistance of any surface film between them (Slade, 2014). Cleaning removes that film to restore contact, but anything left behind after cleaning becomes a new film.

Leakage current follows a slightly different path. When a thin water film forms on a board or terminal and ions are dissolved in it, current leaks between two conductors under voltage and corrosion proceeds. Hygroscopic contamination left on the surface, contamination that draws moisture from the air, plays a large part in building that water film (Ambat et al., 2018). The chill, moisture and residue a cleaner can leave behind lead into one of these two paths, a film on the contact or a water film between conductors, while plastic damaged by the cleaner takes away the force that held the contacts together.

In such cases the technical team sets up the five hypotheses below and rules them out one by one. The start is always the same: find the safety data sheet, the SDS, and the technical data sheet, the TDS, for the cleaner used, check its composition and directions, and log where and how much was sprayed, how long after spraying the power went back on, and the temperature and humidity that day.

Hypothesis 1: chill condensation

Look at this hypothesis first when the air is humid, as in the rainy season or midsummer, when a panel beside equipment in an unconditioned area is worked on with its door open, or when cleaner is sprayed in long bursts at one spot. Picture a rainy-season afternoon and a generous spray of cleaner on the terminal block of a panel standing open. The sprayed area quickly turns cloudy, and it feels colder than its surroundings when the back of a hand is held near it. A few minutes later the solvent smell has gone, but the gaps between terminals still look damp.

Evaporation needs heat, and that heat is drawn from the surface the solvent sits on. A surface where a volatile solvent evaporates quickly therefore becomes colder than the surrounding air, and once its temperature falls below the dew point, the temperature at which water vapour in the air starts to condense, water forms on it. When humid air flows over a polymer solution in a volatile solvent, evaporative cooling makes water droplets condense on the surface, a principle also used to make regular arrays of pores in polymer films (Srinivasarao et al., 2001). In painting, the same effect appears as a defect called blushing, explained as dew forming on the film surface through evaporative cooling or moisture diffusing into the film (Kobayashi et al., 2008). Once condensed water dissolves ionic contamination on the surface, leakage current rises sharply. On test boards contaminated with sodium chloride, surface humidity was raised by increasing chamber humidity or by cooling the boards, and on boards above a certain contamination level, leakage current rose considerably as surface humidity approached the critical humidity of that salt (Verdingovas et al., 2014).

The dew point of the air that day comes first. Measure the temperature and relative humidity around the panel with a thermo-hygrometer to get the dew point, and compare it with the surface temperature of the sprayed spot taken with a contact thermometer right after spraying. If the surface fell below the dew point, the conditions for condensation were there. Watch whether the sprayed area clouds over and whether moisture remains after the solvent smell has gone, and measure insulation resistance between the same terminals right after spraying and again once the surface is back at room temperature.

When condensation looks like the cause, change how the cleaner is applied. Spray in short bursts rather than one long one so the surface does not chill too far, and wait for it to return to room temperature before powering up. On humid days, dehumidify the panel with the door closed or move the work to a drier time of day. Wipe off remaining moisture with a lint-free cloth, and if ionic contamination was present there, wash it off thoroughly first.

Hypothesis 2: redeposited residue

When a contact or board coated with old oil, hardened grease, flux residue from soldering, or grime of sweat and dust got one or two sprays of cleaner and no more, the contamination may simply have settled again. The cleaner dissolves such soil well, but unless there is enough of it to carry what it dissolved away, the contamination only moves. Think of a relay socket covered in dust and oily grime, given a short spray and left. Solvent carrying dissolved grime runs down the board, and once dry, a faint brown band is left across the terminals where the run ended.

The way a liquid dries is what gathers dissolved contamination into a band. When a liquid dries with its edge pinned to the surface, liquid from the interior flows outwards to replace what evaporates at the edge, and this flow carries nearly all the dissolved or suspended material to the edge and piles it up in a ring (Deegan et al., 1997). Contamination that was spread thinly becomes concentrated in a narrow band. Some of this residue draws moisture from the air. Residues of the weak organic acids used as activators in no-clean fluxes each have their own threshold humidity, and above it a water film formed and leakage current jumped by two to four orders of magnitude (Verdingovas et al., 2015). The higher the temperature, the lower the humidity at which flux residues formed a thicker water film (Piotrowska et al., 2019). So a band running across conductors can raise leakage current even at ordinary humidity.

Inspect the edges and lower side of the cleaned area with a magnifier and good light. Look for rings, bands, or white or sticky marks bridging conductors, and for signs of liquid that ran under components or into connector gaps. Compare insulation resistance between terminals with marks and terminals without, and measure the same spot again on a dry day and a humid day; that shows whether the residue reacts to moisture. Which contamination came from where can be narrowed by comparing it with the sources and types of contamination set out in the IPC cleaning guidelines (IPC, 2011).

If bands show up, dissolving is not enough; the soil has to be flushed away. Wet the part thoroughly from top to bottom so dissolved soil runs off the board, and catch the run-off with a cloth. Rinse once more with clean cleaner, wipe with a lint-free cloth or brush, and remove heavily soiled parts for proper cleaning or replace them. Close off the routes by which oil mist and dust get into the panel as well, or the contamination will settle again.

Hypothesis 3: power-up while wet

This hypothesis comes into play when a stopped line must be restarted quickly, when cleaner is forced into a connector gap without unplugging it, or when places where liquid pools easily, such as relay sockets and terminal boxes, are worked on inside a closed enclosure. A night shift with a stopped conveyor is a typical case: the sensor connector is sprayed, pushed straight back in and the power restored. For the first few minutes the signal is erratic and the residual current breaker trips once, but a while later everything runs as if nothing had happened.

Even when the outside looks dry, solvent that got inside a connector housing, under a component or into the thread of a terminal screw has little surface exposed to air and dries far more slowly. That liquid carries dissolved contamination and may also hold water condensed by evaporative cooling. When voltage is applied across a water film with dissolved ions, current leaks between conductors and electrochemical corrosion can take place (Ambat et al., 2018). The risk does not end with leakage current. If the product uses a flammable solvent or propellant, vapour trapped in a closed enclosure can meet the spark of a contact opening or closing. A case has been reported in which a worker cleaning a high-voltage switch compartment sprayed cleaning fluid and the spray became a path for current, setting off an arc (NIOSH, 1987).

Matching the timing is the easiest check. Look in the records for whether the faults bunched up right after power-up and faded over time, and whether the days the cleaner was used line up with the days the breaker tripped. Next time the same job is done, unplug the connector to see whether liquid has pooled inside and whether a solvent smell remains, and measure insulation resistance between the same terminals before switching on. If the value recovers when measured again after full drying, the weight of evidence shifts towards power applied while wet.

If power went on while wet, putting the work sequence right is the answer. Spraying only after the power is isolated and locked out is the baseline, and regulations also require live parts to be de-energised first when work is done on or near them (OSHA, n.d.). Unplug connectors before spraying, tilt or wipe out pooled liquid, open the enclosure door to let vapour out and keep to the drying time the product specifies. Then check insulation resistance before switching on.

Hypothesis 4: damaged plastics

Contacts are surrounded by plastics: connector housings, relay covers, switch bodies and terminal blocks. Suspect plastic damage when cleaner has reached parts held under load by screws or snap fits, when a strong cleaner not checked for plastic compatibility was used, or when parts made of polycarbonate, such as clear covers, were cleaned. One example is a clear terminal cover held down firmly with two screws and drenched in cleaner. Some days later, hairline cracks appear around the screw holes, and from then on contact faults under the cover become more frequent.

Plastics crack when load and chemical act together. Environmental stress cracking is the premature embrittlement and cracking of a plastic under stress when it meets a chemical. The chemical does not break down the molecules; it speeds up cracking driven by the stress, so it can happen without any visible sign of the plastic dissolving (Jansen, 2015). In tests where polycarbonate was held at a fixed bend and immersed in liquids, isopropyl alcohol, methanol and ethylene glycol monomethyl ether all weakened it substantially. The strain at which cracking began was about 1.21% in isopropyl alcohol and about 0.29% in ethylene glycol monomethyl ether, and in the glycol ether the specimen failed completely after about 22 seconds (Al-Saidi et al., 2003). A cracked housing can lose the force that pressed the contacts together, and since contact resistance rises as the area actually touching shrinks, the signal drops in and out (Slade, 2014). Cracks also become channels where moisture and dust collect.

Use a magnifier on the places where load concentrates in plastic parts: screw bosses, snap-fit latches and the edges of metal inserts. Whitened, hazy marks, fine crazing, or a surface that has turned sticky or soft point to the solvent. Check whether the cleaner's TDS lists which plastics it is safe on, and if in doubt, spray a spare of the same part, tightened to the same load, in an inconspicuous spot and leave it for a few days. Measuring contact resistance before and after replacing the housing confirms whether the cracking is tied to the contact fault.

Once damaged plastic is confirmed, cracked parts have to be replaced. To keep it from happening again, choose a cleaner marked as safe on plastics, and rather than spraying covers or housings directly, wet a cloth and wipe only the contacts. Where the cover can be opened to clean the contacts, loosen the screws to take the load off while working, and tighten them again only after the cleaner has fully evaporated.

Hypothesis 5: film-leaving cleaner

A maintenance shelf holds several cans with similar names. Products that only clean sit next to products made to leave a lubricant or protective film as they clean, and general-purpose degreasing solvents end up on contacts too. If contact faults persist stubbornly after cleaning, or the same contact needs attention again at ever shorter intervals, the cleaner itself deserves a closer look. Imagine a maintenance room with two cans of a similar colour side by side. One is a contact cleaner, the other a contact cleaner and lubricant, and in a hurry whichever comes to hand first is used.

Being called a contact cleaner does not mean a product evaporates without a trace. Products that mix a lubricating mineral oil into high-purity solvents, products made to leave a thin silicone film and slow-drying formulations are all sold for contacts (MG Chemicals, n.d.). Such films are meant to protect moving parts, but when left between contacts they add a film resistance to the resistance of the touching spots (Slade, 2014). Even a solvent made to evaporate can contain nonvolatile matter, the part that remains after full evaporation, which is why a standard test exists for volatile paint solvents that evaporates the solvent, dries the remainder at a set temperature and weighs it (ASTM International, 2021).

Start with the can and the SDS. Check whether the name or composition mentions lubricant, protective film, oil or silicone, and whether the description of use says it leaves a film. Spray a little of the same cleaner on clean glass or a mirror, let it dry completely and see whether a pattern or greasy trace remains. Cleaning the same contact again with a cleaner that leaves no film and comparing contact resistance or signal condition reveals the effect of the film, and if the amount left behind needs a number, send the product to a laboratory for an evaporation residue test.

If a film is to blame, separate cleaning and lubrication into different jobs. Keep cleaning cans apart from lubricating and protective cans and label them clearly, and use a cleaner confirmed to leave no residue on signal contacts. Apply the specified lubricant thinly as a separate step after cleaning on sliding contacts or potentiometers that need it, and flush contacts already coated with a film thoroughly with a cleaner that leaves none before putting them back into service.

Finding the cause

Five hypotheses do not mean five separate investigations. Start with what can be ruled out just by asking and looking. The can and its SDS are at hand, and the time of spraying, the time of power-up and that day's humidity are in the work log and equipment records. Those two alone go a long way towards telling whether the cleaner leaves a film and whether power went on before things were dry.

Next come the timing and pattern of the fault. If it bunched up right after power-up and faded as things dried, look at power-up while wet or condensation. If it returns on every humid day and bands are visible between terminals, suspect redeposited hygroscopic contamination. If there is no leakage but a contact fault that will not go away, the film left on the contact or a cracked housing is the more likely side.

If that still does not settle it, run a control trial. Pick two contacts of the same type, leave one as usual and change one thing on the other: first only full drying before power-up, then the cleaner, then the amount of flushing. Change only one thing at a time, or there is no telling which one worked, and compare insulation resistance and contact condition at the two spots on the same day at the same humidity.

The final check is in numbers. After cleaning with the revised method, measure insulation resistance between the same terminals again on a dry day and a humid day, and see whether fault records for the affected circuit have stayed clear for a set period. The cause is gone only when the values hold on humid days as well as dry ones.

The hypotheses can overlap. When water condensed by evaporative cooling dissolves redeposited hygroscopic residue, leakage current can be far higher than when water forms on a clean surface (Verdingovas et al., 2014), and applying power on top of that can start corrosion. In such cases, put thorough flushing and full drying right first, then look at the type of cleaner and at plastic damage, because while moisture and residue remain, the effect of changing the cleaner cannot be compared fairly.

Limits and cautions

A cleaner's composition, drying time and the plastics it is safe on differ by product, so numbers and directions follow that product's TDS and SDS and the equipment maker's maintenance instructions. Expensive control boards, safety circuits and high-voltage equipment should not go back into service on floor cleaning and judgement alone; get the equipment maker or a specialist to confirm, and base any new board cleaning process on industry guidelines (IPC, 2011).

Safety matters too. Keep aerosol cleaners marked as flammable away from flames and heat sources, and never spray them on live parts. The investigation report on a case in which spray in a high-voltage switch compartment became a path for current recommended banning aerosol cans from high-voltage rooms (NIOSH, 1987). n-Hexane used in some aerosol degreasers was linked to peripheral nerve damage among motor mechanics, leading to recommendations to reformulate products and use more aqueous cleaning, and latex gloves give poor protection against organic solvents (CDC, 2001). Use cleaners where there is ventilation, and wear gloves suited to the solvent and eye protection.

Sources

  1. Al-Saidi, L. F., Mortensen, K., & Almdal, K. (2003). Environmental stress cracking resistance. Behaviour of polycarbonate in different chemicals by determination of the time-dependence of stress at constant strains. Polymer Degradation and Stability, 82(3), 451–461. https://doi.org/10.1016/S0141-3910(03)00199-X
  2. Ambat, R., Conseil-Gudla, H., & Verdingovas, V. (2018). Corrosion in electronics. In K. Wandelt (Ed.), Encyclopedia of interfacial chemistry (pp. 134–144). Elsevier. https://doi.org/10.1016/B978-0-12-409547-2.13437-7
  3. ASTM International. (2021). ASTM D1353-13(2021), Standard test method for nonvolatile matter in volatile solvents for use in paint, varnish, lacquer, and related products. https://store.astm.org/d1353-13r21.html
  4. Centers for Disease Control and Prevention [CDC]. (2001). n-Hexane-related peripheral neuropathy among automotive technicians: California, 1999–2000. Morbidity and Mortality Weekly Report, 50(45), 1011–1013. https://www.cdc.gov/mmwr/preview/mmwrhtml/mm5045a3.htm
  5. Deegan, R. D., Bakajin, O., Dupont, T. F., Huber, G., Nagel, S. R., & Witten, T. A. (1997). Capillary flow as the cause of ring stains from dried liquid drops. Nature, 389(6653), 827–829. https://doi.org/10.1038/39827
  6. IPC. (2011). IPC-CH-65B, Guidelines for cleaning of printed boards and assemblies. IPC.
  7. Jansen, J. A. (2015). Plastic failure through environmental stress cracking. Plastics Engineering. https://www.madisongroup.com/publications/JansenESC%20Article.pdf
  8. Kobayashi, H., Francis, L. F., & Scriven, L. E. (2008). Effect of humidity on the surface deformation. 14th International Coating Science and Technology Symposium, Marina del Rey. https://www.iscst.com/wp-content/uploads/2015/05/Kobayashi_ISCST08.pdf
  9. MG Chemicals. (n.d.). Ultimate guide to electronic cleaners: Optimizing performance & service life. Retrieved November 2026. https://mgchemicals.com/knowledgebase/ultimate-guide-to-electronic-cleaners-optimizing-performance-service-life/
  10. National Institute for Occupational Safety and Health [NIOSH]. (1987). 28-year-old electronic technician dies from electrical burns in Georgia, FACE 87-31. https://stacks.cdc.gov/view/cdc/164532
  11. Occupational Safety and Health Administration [OSHA]. (n.d.). 29 CFR 1910.333, Selection and use of work practices. U.S. Department of Labor. Retrieved November 2026. https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.333
  12. Piotrowska, K., Grzelak, M., & Ambat, R. (2019). No-clean solder flux chemistry and temperature effects on humidity-related reliability of electronics. Journal of Electronic Materials, 48, 1207–1222. https://doi.org/10.1007/s11664-018-06862-4
  13. Slade, P. G. (Ed.). (2014). Electrical contacts: Principles and applications (2nd ed.). CRC Press.
  14. Srinivasarao, M., Collings, D., Philips, A., & Patel, S. (2001). Three-dimensionally ordered array of air bubbles in a polymer film. Science, 292(5514), 79–83. https://doi.org/10.1126/science.1057887
  15. Verdingovas, V., Jellesen, M. S., & Ambat, R. (2014). Impact of NaCl contamination and climatic conditions on the reliability of printed circuit board assemblies. IEEE Transactions on Device and Materials Reliability, 14(1), 42–51. https://doi.org/10.1109/TDMR.2013.2293792
  16. Verdingovas, V., Jellesen, M. S., & Ambat, R. (2015). Relative effect of solder flux chemistry on the humidity related failures in electronics. Soldering & Surface Mount Technology, 27(4), 146–156. https://doi.org/10.1108/SSMT-11-2014-0022

Product and site consultation

Leave your company, site and the product groups in use. Our engineer will get in touch to go through your site conditions and concerns. Materials, equipment, operating conditions and downstream steps show what should change and what can stay. If nothing needs to change, we will say so.

Contact us
After you contact us
  1. 01
    Site setup

    We confirm process conditions and needs first.

  2. 02
    Spec design

    We set the product spec and selection criteria.

  3. 03
    Comparison

    We compare matching candidates and propose.

  4. 04
    Tailored supply

    We supply on time and manage the stock.

  5. 05
    Site check

    We visit, check conditions of use and record.

  6. 06
    Use management

    We track use and change cycles to catch issues.

  7. 07
    Regular analysis

    We analyze the records and send a yearly report.