Why is refrigeration oil turning acidic and dark?

Type
Application notes
Published
23 November 2026
Prepared by
Jonghwan Moon
Product group
Equipment/Service Lubricants

Changing the oil is the usual response when refrigeration oil turns acidic, but if the water, air and heat that made the acid stay in the system, the new oil's acid number climbs again. What actually lies behind it can be moisture breaking down POE oil, poor evacuation, high discharge temperature, motor burnout residue or a saturated filter drier, and sometimes two or more at once.

Background

At a routine service, a little oil drawn from the refrigeration compressor has turned from a clear yellow to a dark brown. The acid test kit changes colour too, pointing to acid. Change the oil, measure again a few months later, and the acid number has risen once more, while the temperature around the expansion valve has started to wander or the compressor motor's insulation resistance has begun to fall.

Acid eats the system from the inside. The way a refrigeration system's oil and refrigerant deteriorate under long stress shows up as changes in acidity, moisture, viscosity and dissolved metal, and all of these are tied to acid that builds up over time. Acid dissolves metal into salts and sludge, and when these collect in narrow places such as capillary tubes or expansion valves, flow is choked and the system can fail. Acid also builds slowly at first, then past a certain point begins to form exponentially faster (Cartlidge & Schellhase, 2003). Acid and sludge left behind by a motor burnout can attack the windings of the replacement compressor and cause another burnout (Young, 2019).

Where the acid comes from depends on the pairing of oil and refrigerant. In older systems running chlorine-containing CFC or HCFC refrigerants with mineral oil, the main acids were hydrochloric and hydrofluoric acid from refrigerant breaking down at high temperature. Chlorine-free HFC refrigerants are far more stable and make almost none of these strong acids, but the polyol ester, or POE, oil used with them reacts with water to make weak organic acids. Total acid number, or TAN, measures both kinds together, which makes it a good indicator of system condition. For mineral oil systems 0.05 mg KOH/g became the action level, but the industry has no agreed level yet for POE systems, which is expected to sit higher than for mineral oil (Cartlidge & Schellhase, 2003).

In such cases the technical team sets up the five hypotheses below and rules them out one by one. The start is always the same: measure acid number, moisture and colour on one oil sample, log the refrigerant and oil types, recent repair and evacuation records, compressor replacement history, discharge temperature and condensing pressure, and compare them with the oil's technical data sheet, the TDS, and the equipment maker's limits.

Hypothesis 1: wet POE oil

In a system running HFC refrigerant with POE oil, suspect moisture first. It applies when the system has been left open for a long repair on a humid day, when the top-up oil drum was used with its lid off, and when leftover oil was reused on a later job. One rainy-season afternoon, the system was left open for half a day to repair piping on a rooftop unit, with an open drum of POE oil standing on the bench. The repair went well, but an oil sample taken a few months later turns the acid test kit.

POE is vulnerable to moisture for two reasons. One is that it takes up water readily: POE saturates at about 2,500 ppm of water, far above about 25 ppm for mineral oil. The other is hydrolysis. POE is an ester made by reacting acids with alcohols, so when it meets water that reaction runs backwards and it returns to the parent organic acids and alcohols. In the pure state this is very slow, but acids, bases and metals speed it up, it accelerates sharply as temperature rises, and acid formed early on drives the reaction further. Each unit of water that reacts makes acid, so the amount of acid depends mainly on the amount of water that got in. The organic acids react with system metals to form salts that can plug capillary tubes, and the alcohol formed alongside can carry contaminants around the system (Cartlidge & Schellhase, 2003).

Checking starts with how much water is in the oil. Take the sample without exposing it to air and measure it by Karl Fischer titration, a quantitative method for water, which reads down to mg/kg levels (ASTM International, 2025). Measure acid number on the same sample to see whether moisture and acid are high together. If the liquid line has a moisture-indicating sight glass, record its colour too, and find in the job records when the system was last opened, the weather that day, and which container the top-up oil came from and how much went in.

If moisture comes out high, getting water out of the system comes first. Fit a new filter drier and, if needed, recover the refrigerant and evacuate again to pull the water out. If acid number is high, renew the oil as well. Buy POE oil in small sealed containers, open only what is needed, and do not use oil left in an opened container on the next job. Keep the time the system stands open short, and cap pipe ends on humid days.

Hypothesis 2: poor evacuation

When acid starts rising right after installation or repair, the evacuation done at the time comes under suspicion. Typical cases are a vacuum pump run only briefly before charging, evacuation ended by the clock without a vacuum gauge, and a system run with a leak. Picture a rushed compressor replacement. To hold the cold store's temperature overnight, the vacuum pump ran only a short while before the refrigerant went in. The machine runs again, but from then on condensing pressure reads higher than before and the compressor shell feels hotter.

A refrigeration system is sealed, but if evacuation falls short or there is a leak, oxygen stays behind or gets in. Mineral and alkylbenzene oils too, with residual air, oxidise at high temperature into small organic acids such as formic and acetic acid. In sealed tube tests with added contaminants and in long compressor runs, organic acid and water each increased corrosion, the breakdown was greatly accelerated when air was present, and air produced precipitate (Cartlidge & Schellhase, 2003). Unlike refrigerant, air is a non-condensable gas that does not liquefy in the condenser, so it drives condensing pressure up. In an R134a chest freezer experiment, 3.3% air raised power consumption by 37.1% and cut the coefficient of performance by 42.8%, and compressor temperatures rose with the air content (Ali et al., 2025). Non-condensable gas gets in through improper installation or service, adds load on the compressor and shortens its life (Hu & Yuill, 2023). Moisture that comes in with the air also feeds the POE hydrolysis described above.

Open the job records first. See how long evacuation ran, to what vacuum level, and whether a hold test was done to check that the vacuum held after the pump stopped. In the running records, compare whether condensing pressure and discharge temperature at the same outdoor temperature are higher than before the repair. With the machine stopped and left until the condenser and refrigerant are at room temperature, a condenser pressure clearly above the refrigerant's saturation pressure at that temperature points to non-condensable gas. Run a leak check as well, to see whether there is a path that keeps letting air in.

If non-condensable gas is confirmed, take the refrigerant out with recovery equipment, evacuate to the vacuum level the manufacturer specifies while watching a vacuum gauge, pass a hold test and recharge. Change the filter drier at the same time, and the oil too if acid number is high. If a leak was found, fix it before evacuating. From the next job on, have the vacuum level reached and the hold test result recorded rather than the time spent.

Hypothesis 3: hot discharge

When the machine keeps running hot, oil and refrigerant age quickly. Discharge temperature rises when condenser fins clog with dust, when hot air pools around an outdoor unit in midsummer, when a short charge sends suction gas back overheated, and when low suction pressure raises the compression ratio. On a summer afternoon, a rooftop unit's condenser fins are thick with dust and pollen, and the insulation near the compressor discharge line has yellowed and cracked. Oil drawn from it is visibly darker than from the other machines.

Chemical reactions speed up as temperature rises. Refrigerant breakdown is very small in normal running, but its rate climbs sharply with temperature, and chlorine-containing refrigerants then produce significant hydrochloric and hydrofluoric acid that corrode metals and leave salts and deposits. HFCs also break down a little at high temperature and release hydrofluoric acid, but far less. POE hydrolysis likewise speeds up with temperature, and in sealed tube tests with metal coupons, the more contaminant and the higher the temperature, the faster iron coupons darkened and lost weight (Cartlidge & Schellhase, 2003). Low global warming potential HFO refrigerants carry a double bond in the molecule that makes them less chemically stable than HFCs, and POE oils with additives reformulated for them are being developed (Tada et al., 2016). Heat changes acid and colour together. Oil turning darker can be a sign of more thermal breakdown products and more dissolved metal.

Measure discharge temperature with a contact thermometer on the discharge line close to the compressor outlet and compare it with the compressor maker's limit. Logging suction and condensing pressure and suction superheat alongside it shows which side pushed the temperature up. Check condenser fins for clogging, fan rotation and airflow around the outdoor unit by eye, and record readings from the hot and cool parts of the day side by side. Rating oil colour against the standard colour scale and keeping the number makes it easy to compare machines and periods (ASTM International, 2024a).

If temperature is the cause, start by bringing the heat down. Clean the condenser, put the fans and airflow right, and check the refrigerant charge against the maker's figure. If suction pressure is low, look for blockage on the evaporator side or at the expansion valve setting. If acid number is still high after the temperature is fixed, change the oil and filter drier, and watch whether acid and colour climb again by the next service. Where the refrigerant has been changed, confirm with the supplier that the oil suits that refrigerant.

Hypothesis 4: burnout residue

In a system whose compressor was replaced after a motor burnout, start by asking how thoroughly it was cleaned up at the time, all the more if the replacement was rushed and the clean-up skipped, no suction-line filter drier was fitted, or the old oil and drier were left in. It shows up in a machine a few weeks after a burnout replacement. The new compressor's oil has already darkened to brown, the sample smells burnt, and black oily residue comes out along the suction piping.

The heat of a motor burnout breaks part of the oil and refrigerant down into acids and sludge that contaminate the system. Unless these contaminants are removed, they will probably attack the windings of the replacement compressor motor and cause another burnout (Young, 2019). Analysis of refrigerant and oil from field systems found that compressor oil from burned-out R-22 systems averaged an acid number of 0.38 mg KOH/g, far above the 0.04 mg KOH/g average for oil in normal use, and contained mineral acids such as hydrochloric acid alongside organic acids (Cartlidge & Schellhase, 2003). Sludge formed as acid dissolves metal can, as noted above, plug capillary tubes and expansion valves. So dark, acidic oil after a burnout can be residue that keeps dissolving back into the oil.

The replacement job record is the place to start. Confirm whether a suction-line filter drier was fitted, whether the liquid-line drier was changed and whether the old oil was drained. Draw oil from the new compressor, check it with an acid test kit, and note its smell and colour. If a suction-line filter drier is fitted, measure the pressure drop across it to see whether sludge is clogging it. If the oil is too dark for the kit's colour change to be read, send it to a laboratory for acid number by potentiometric titration (ASTM International, 2024b).

If residue appears to remain, clean up again. Take the refrigerant out with recovery equipment, fit a suitable suction-line filter drier, renew the liquid-line drier or its core, drain the old oil and fill with new. After a day or two of running, remove the suction-line drier and change the liquid-line drier again, then check an oil sample with the test kit; if it is still acidic, change the oil again, run for about another day and retest (Young, 2019). Look for the cause of the first burnout as well, so it does not repeat.

Hypothesis 5: saturated filter drier

If the filter drier has never been changed while the system was opened and closed many times, it may have no room left to hold more water. The same goes for a drier undersized for the system, or a large leak or repair that let in a lot of water at once. Take a machine that has had several leak repairs and top-ups over a few years. The moisture indicator in the liquid-line sight glass always sits at the warning colour, and the oil's acid number is a little higher at each change.

The desiccant in a drier, such as molecular sieve, is not meant to remove all water from the system but to hold the water POE is exposed to at a low level and so restrict how much acid forms. In long compressor runs with R-134a and POE at about 50 ppm moisture, acid number passed 0.7 mg KOH/g after 4,000 hours without a drier but averaged only 0.1 mg KOH/g with one (Cartlidge & Schellhase, 2003). The same report notes that desiccants also remove some of the acid, mainly inorganic acid. There is a limit, though, to how much water a drier can hold. Drier performance is rated by the water it holds in equilibrium with refrigerant at a set temperature and by the lowest moisture level it can dry the refrigerant to, while acid removal is not rated (AHRI, 2009). A drier past that limit cannot hold any more incoming water, so the water keeps circulating with the oil and refrigerant and keeps making acid.

Count from the service records when the drier was last changed and how many times the system was opened since. Check the moisture indicator colour in the liquid-line sight glass while running, and measure moisture in the oil and refrigerant to keep as before-change values. A large temperature or pressure difference across the drier means it is clogging with debris, so check that too. Confirm against the maker's selection table that the drier size suits the system's charge and capacity.

Replace a drier that is past its limit, and from then on make changing it every time the system is opened standard practice. If it was undersized, step up a size. If acid number is already high, review with the maker the temporary use of a drier able to remove acid, and change the oil along with it. After the change, check the moisture indicator and acid number again at intervals of a few weeks to confirm they are falling.

Finding the cause

The effort needed to sort the five hypotheses differs widely. Measuring acid number, moisture and colour on one oil sample and opening the job records can be done without stopping the machine. Discharge temperature and condensing pressure are read while it runs. Recovering refrigerant to re-evacuate, or changing the drier, means opening the system, so do it after the earlier checks have narrowed the cause.

The combination of readings points the way. If acid number and moisture are both high, look first at moisture breaking down POE and at drier saturation, and lean towards the drier if the moisture indicator has long sat at the warning colour. If acid is high but moisture low, and condensing pressure and discharge temperature have been higher since a repair, suspect air left by poor evacuation. Dark oil with a burnt smell soon after a compressor change points to burnout residue, and high discharge temperature at certain seasons or times of day with oil darker in that machine alone points to heat.

There is a caution when reading oil colour. Test kits and indicator titration read acid from a colour change, so with very dark oil the end point can be masked and misread (ASTM International, 2022). In that case, measure by potentiometric titration (ASTM International, 2024b). The trend of acid numbers measured the same way says more than any single value, so take samples from the same point by the same method each time.

Once the cause has narrowed, change one thing and watch the result. Change only the drier and remeasure moisture and acid a few weeks later; clean the condenser and see whether discharge temperature falls; re-evacuate and see whether condensing pressure comes back. Change several things at once and there is no telling which worked. The job is done only when the new oil's acid number stays below its earlier trend measured the same way, the moisture indicator returns to its normal colour and the oil stops darkening.

The hypotheses are intertwined. Poor evacuation leaves moisture along with air; air raises condensing pressure and compressor temperature (Ali et al., 2025); and heat and moisture in turn drive POE hydrolysis. Acid that builds up and damages motor insulation leads to a burnout, and a burnout leaves acid and sludge again (Young, 2019). In such cases, remove the contaminants first, which means recovering the refrigerant, evacuating properly, fitting a new drier and filling new oil, and then correct the running conditions that raised discharge temperature. While contaminants remain, the effect of fixing the running conditions cannot be judged fairly.

Limits and cautions

Action levels for acid number, discharge temperature limits, and drier size and change intervals differ by refrigerant, oil and compressor, so numeric decisions follow the oil's TDS and the compressor and equipment makers' guidance. With no industry consensus on acid limits for POE systems, judge by the trend measured the same way rather than a single value. Refrigerant recovery, evacuation and compressor replacement are for technicians qualified to handle refrigerants, working under local regulations, and refrigerant is never vented.

Oil and refrigerant from a burned-out system can contain acid that burns eyes and skin, so wear safety glasses and chemical-resistant gloves, and put drained oil into separate, labelled containers (Young, 2019). Handle oils, refrigerants and test reagents according to the product's safety data sheet, the SDS, and isolate and lock out power before work. Systems using flammable refrigerants follow the separate safety procedures set by the manufacturer.

Sources

  1. Air-Conditioning, Heating, and Refrigeration Institute [AHRI]. (2009). ANSI/AHRI Standard 710 (I-P), 2009 standard for performance rating of liquid-line driers. https://www.ahrinet.org/search-standards/ahri-710-i-p2009-performance-rating-liquid-line-driers
  2. Ali, H. M., Kadhim, S. A., Hammoodi, K. A., Ashour, A. M., Hassan, A. M., Alomari, M. A., & Askar, A. H. (2025). Exploring the influence of air fractions on the performance of a vapor compression refrigeration system: An energy, exergy, and environmental analysis. International Journal of Air-Conditioning and Refrigeration, 33. https://doi.org/10.1007/s44189-025-00079-x
  3. ASTM International. (2022). ASTM D974-22, Standard test method for acid and base number by color-indicator titration. https://store.astm.org/d0974-22.html
  4. ASTM International. (2024a). ASTM D1500-24, Standard test method for ASTM color of petroleum products (ASTM color scale). https://store.astm.org/d1500-24.html
  5. ASTM International. (2024b). ASTM D664-24, Standard test method for acid number of petroleum products by potentiometric titration. https://store.astm.org/d0664-24.html
  6. ASTM International. (2025). ASTM D6304-25, Standard test method for determination of water in petroleum products, lubricating oils, and additives by coulometric Karl Fischer titration. https://store.astm.org/d6304-25.html
  7. Cartlidge, D., & Schellhase, H. (2003). Using acid number as a leading indicator of refrigeration and air conditioning system performance (Final Report ARTI-21CR/611-50060-01). Air-Conditioning and Refrigeration Technology Institute. https://www.osti.gov/biblio/823889
  8. Hu, Y., & Yuill, D. P. (2023). Non-condensable gas in the refrigerant of air-source heat pumps: Interactions between detection features, charge level, and temperature. International Journal of Refrigeration, 153, 378–384. https://doi.org/10.1016/j.ijrefrig.2022.10.006
  9. Tada, A., Okido, T., & Sakamoto, K. (2016). Development of polyol ester refrigeration oils for HFO refrigerants. In International Refrigeration and Air Conditioning Conference (Paper 1732). Purdue University. https://docs.lib.purdue.edu/iracc/1732
  10. Young, S. (2019). System clean up after compressor motor burn out (Publication R-080). J & E Hall International. https://jehall.com/files/ww/HSQE/r-080-system-clean-up-after-compressor-motor-burn-out.pdf

Product and site consultation

Leave your company, site and the product groups in use. Our engineer will get in touch to go through your site conditions and concerns. Materials, equipment, operating conditions and downstream steps show what should change and what can stay. If nothing needs to change, we will say so.

Contact us
After you contact us
  1. 01
    Site setup

    We confirm process conditions and needs first.

  2. 02
    Spec design

    We set the product spec and selection criteria.

  3. 03
    Comparison

    We compare matching candidates and propose.

  4. 04
    Tailored supply

    We supply on time and manage the stock.

  5. 05
    Site check

    We visit, check conditions of use and record.

  6. 06
    Use management

    We track use and change cycles to catch issues.

  7. 07
    Regular analysis

    We analyze the records and send a yearly report.