Why is RO permeate conductivity creeping up?

Type
Application notes
Published
23 November 2026
Prepared by
Jonghwan Moon
Product group
Water & Waste Treatment

Cleaning the membranes, or replacing them as worn out, is the usual response when RO permeate conductivity rises, but depending on the cause cleaning brings nothing back and new membranes can go the same way. What actually drives conductivity up can be membrane oxidation by residual chlorine, leaking O-rings and seals, concentration polarisation raised by scale and fouling, warm feed water, or damage during cleaning, and sometimes two or more at once.

Background

In an RO unit making boiler make-up or process water, the permeate conductivity logged every day creeps up over a few weeks. The ion exchange downstream needs regenerating more often, and once the water exceeds what the process requires, permeate has to be dumped or the line stopped. Replacing membranes without knowing the cause can mean paying for them and then seeing the same trend again a few months later.

In an RO membrane, water and salt pass under different driving forces. Water passes in proportion to the applied pressure minus the osmotic pressure, while salt diffuses across following the concentration difference on either side and is hardly affected by pressure (Wijmans & Baker, 1995). So permeate conductivity rises when the membrane lets more salt through, when less water is there to dilute the same salt, or when water that never crossed the membrane mixes into the permeate.

Conductivity also moves with temperature, feed concentration and recovery, so only normalisation, recalculating operating data to reference conditions, separates a change in the membrane itself (ASTM International, 2019). When normalised salt passage rises, whether permeate flow rose with it, held steady or fell splits the likely causes sharply (DuPont, 2021).

In such cases the technical team sets up the five hypotheses below and rules them out one by one. The start is always the same: plot the trends of normalised permeate flow, salt passage and differential pressure, and measure permeate conductivity from each pressure vessel to see whether the high reading covers a whole stage or a single vessel.

Hypothesis 1: chlorine oxidation

If the raw water is disinfected with chlorine, ask whether dechlorination ahead of the membranes ever lapsed. That includes an activated carbon filter left too long without renewal, a sodium bisulfite dosing pump that stopped or a chemical tank that ran dry, and too little rinsing after pipework was disinfected with chlorine; mains water carrying chloramine together with iron belongs here too. Picture a unit whose sodium bisulfite dosing pump has been stopping and restarting for several weeks without anyone noticing. Over those weeks the permeate conductivity of the first-stage vessels starts rising ahead of the later stage, and normalised permeate flow creeps up a little.

The thin aromatic polyamide layer on the membrane surface that separates salt is vulnerable to oxidants. Free chlorine attaches to the nitrogen of the amide bond and to the aromatic ring, and as these changes accumulate the polymer chains break (Gohil & Suresh, 2017). In one study, once hypochlorous acid exposure passed a threshold, the membrane's ability to separate water from salt fell permanently (Ettori et al., 2011). Chloramine is no safe harbour either: experiments found that polyamide membranes oxidised faster when ferrous iron was present with monochloramine (Gabelich et al., 2005).

A manufacturer's manual states that damage begins after roughly 200 to 1,000 hours of exposure to 1 mg/L free chlorine, with permeate flow first dipping slightly and then permeate flow and salt passage rising together. The same manual notes that heat and metals such as iron speed the attack, and that when an oxidant is in the feed the lead elements suffer most (DuPont, 2021).

The dechlorination record is the first evidence. Line up by date the trend of oxidation-reduction potential, the ORP, after the reducing agent injection point, the dosing pump run log and the chemical tank level, and measure residual chlorine in the membrane feed directly with a portable meter. If normalised permeate flow and salt passage rise together and the first stage is worse, the evidence leans towards oxidation. Unlike a mechanical leak, oxidation may not show up in a vacuum test, so confirmation needs an autopsy: open one element and have the membrane dye-tested and analysed (DuPont, 2021).

Oxidised membranes cannot be restored by cleaning; replacing the damaged elements is all that remains. Before that, stop it recurring. Fit an ORP meter after the reducing agent injection and interlock it to stop the high-pressure pump when an oxidant is detected, and put a low-level alarm on the chemical tank. Set and keep a renewal interval for activated carbon, and after disinfecting pipework, measure to confirm no residual chlorine before sending water to the membranes.

Hypothesis 2: O-ring and seal leaks

This hypothesis moves to the front right after elements have been installed, or removed for cleaning and reloaded; in units with frequent water hammer, the sudden pressure surge at start-up and shutdown; and where elements still have room to shift back and forth inside the pressure vessel. Think of the day after elements were replaced at a scheduled shutdown. One pressure vessel alone gives clearly higher permeate conductivity than the others in its stage, while its permeate flow is much the same as theirs.

Each element's permeate tube joins the next element through an interconnector fitted with O-rings, and at both ends of the pressure vessel an adapter joins it to the permeate piping outside. When an O-ring is missing, badly fitted or pushed out of place, or has been damaged by chemicals or by an element shifting under water hammer, feed or concentrate enters the permeate tube without crossing the membrane. Feed-side pressure is far higher than permeate-side pressure, so salty water is forced through even a small gap, giving the pattern of salt passage rising while permeate flow stays about the same (DuPont, 2021). A standard likewise defines a leak as a direct path from feed or concentrate to permeate and sets out separate tests for it (ASTM International, 2023).

Probing narrows the location most directly. With the high-conductivity vessel still running, push a plastic tube about 6 mm across to the far end of the permeate tube, then withdraw it step by step, measuring permeate conductivity at each position. A sudden jump at an interconnector marks that O-ring as leaking, and the end adapters are checked the same way. Isolate the probed vessel from the permeate manifold so permeate from other vessels does not mix in (DuPont, 2021). Removed elements can be checked separately for leaks in the element itself with a vacuum test or a dye test (ASTM International, 2023).

Where probing finds a leak, replace the O-rings on that interconnector or adapter and look for cracks, swelling or flattening as well. Each time elements are loaded, confirm every O-ring is in place, and fit shims so the elements cannot move inside the vessel. To cut water hammer, vent air thoroughly before start-up and raise pressure slowly, and keep vessels from draining or going under vacuum during shutdowns. After the repair, probe the same vessel again to confirm the profile is even.

Hypothesis 3: scale and fouling

If permeate flow is falling and differential pressure rising while conductivity climbs, check whether something has built up on the membrane surface. Typical cases follow a recovery increase, a lapse in antiscalant dosing, a rise in raw water hardness, turbidity or iron, or a longer gap between cleanings. One example is a unit whose raw water hardness has gone up while recovery was left unchanged. Differential pressure across the last stage edges upwards, and permeate conductivity climbs as normalised permeate flow falls.

Water crossing the membrane leaves its salt at the membrane surface, so salt concentration near the surface rises above that of the passing feed; this is concentration polarisation. Greater polarisation widens the concentration difference across the membrane so more salt leaks through, and raises the osmotic pressure at the surface so less water passes (Sablani et al., 2001). When a fouling layer such as colloids builds up on the membrane, it blocks salt from diffusing back into the flow and polarisation grows further; in experiments this effect cut permeate flow and lowered salt rejection (Hoek & Elimelech, 2003). Less water passes while the salt leaking through holds steady or grows, so the permeate turns saltier.

Scale adds crystals to this process. As water leaves towards the concentrate end, sparingly soluble salts such as calcium carbonate or calcium sulfate exceed their solubility and grow as crystals on the membrane, blocking both flow and diffusion (Antony et al., 2011). So scaling usually appears first in the last stage, while colloidal and metal oxide fouling gathers mainly in the first stage (DuPont, 2021).

Stage-by-stage data show where to look. Plot permeate flow and differential pressure for the first and last stages separately to see which deteriorated first, alongside the feed turbidity indices and cartridge filter change records. Measure calcium, sulfate, silica and pH in the concentrate, calculate the Langelier index, which expresses how strongly calcium carbonate tends to precipitate, and pull the last element to weigh it or inspect its surface. Scale feels rough like sandpaper and does not wipe off, and fizzing under a drop of acid marks it as carbonate (DuPont, 2021).

Remove the deposit with a cleaning suited to its type, and see whether normalised salt passage returns close to its initial value. If it does, fix the cause: for calcium carbonate scale, reset feed pH and antiscalant dosing; for sulfate scale, reset recovery; for colloids and iron, start with turbidity and iron control in pretreatment. Any share that does not return after cleaning signals membrane damage on top, so look at oxidation and cleaning damage as well.

Hypothesis 4: warm feed water

In summer, where raw water pipes or tanks sit in the sun, where hot process water or cooling water mixes into the raw water, or where feed is warmed by a heat exchanger, first see whether conductivity rises and falls with water temperature. Mid-summer afternoon readings come in higher than the same morning's and drop again overnight. As autumn sets in, the same unit's permeate conductivity returns to its spring level.

As temperature rises, both water and salt move through the membrane faster. A study testing two brackish water RO membranes at 15, 25 and 35 °C found that water permeability and salt permeability both increased with temperature, and that observed salt rejection fell further than the model predicted. Concentration polarisation in the same study actually decreased, so the change came from the membrane itself letting more salt through (Jin et al., 2009). Salt moves by diffusion down the concentration difference, so lowering pressure to hold permeate flow leaves the faster salt diffusion untouched (Wijmans & Baker, 1995).

Overlaying the temperature log on the conductivity log on one chart separates this quickly. If salt passage normalised to a reference temperature stays flat while measured conductivity alone rises and falls with temperature, the membrane is unchanged and the water is what changed (ASTM International, 2019). If the normalised value rises too, temperature is only part of the story, so move to the other hypotheses. Normalisation is only as good as the feed thermometer, so check it once against a portable one.

If temperature is to blame, the fix lies in water quality margin, not the membrane. When summer permeate exceeds its target, lower recovery to reduce concentration on the feed side, or shorten the regeneration interval of the downstream ion exchange for summer, and where warm water mixes into the raw water, review where it joins and how it is cooled. High-temperature operation can also compact the membrane and permanently reduce permeate flow, so do not exceed the manufacturer's maximum operating temperature (DuPont, 2021).

Hypothesis 5: cleaning damage

If conductivity stepped up straight after a cleaning, suspect the cleaning itself. This covers an unstable cleaning solution heater, a long soak in a high-pH solution, a cleaning tank filled with mains water still carrying chlorine, use of an oxidising disinfectant, and cleaning solution run against the normal flow direction. On the day the unit restarts after an alkaline cleaning prompted by rising differential pressure, permeate flow comes back well above its pre-cleaning level, yet conductivity reads higher than before the cleaning, and the cleaning log has no entry for solution temperature or soak time.

Polyamide membranes are fairly tolerant of pH and temperature, but the pH range they withstand narrows as temperature rises. One manufacturer's table allows the same membrane pH 1 to 13 at 25 °C but only 1 to 10.5 at 45 °C, and notes that disinfecting with oxidising chemicals outside the pH and temperature limits, or with metals such as iron catalysing oxidation, can damage the whole membrane evenly. It advises extreme cleaning outside the guidelines only as a last resort because it can damage the membrane, and says large elements must be cleaned in the normal flow direction to avoid telescoping, where the wound membrane layers slide out along the axis (DuPont, 2021). In tests cleaning nanofiltration membranes with caustic soda, membrane pores widened and permeability and salt passage rose, to an extent that varied greatly by membrane type (Simon et al., 2013).

Set the cleaning log beside the operating data. Confirm the cleaning solution's pH, temperature, recirculation and soak times and the source of the make-up water, and compare normalised permeate flow and salt passage just before and after the cleaning. If only certain vessels deteriorated, locate the problem by probing and check removed elements for mechanical damage with a vacuum test (ASTM International, 2023). If permeate flow and salt passage rose evenly together across the whole unit, chemical damage is more likely, and again an element autopsy confirms it (DuPont, 2021).

From the next cleaning on, tie down the procedure. Write the pH and temperature limits and the maximum soak time for each membrane type into the procedure, and fit instruments to measure solution temperature and pH and record them every time. Fill the cleaning tank with chlorine-free permeate, and lock the valves that reverse the flow direction. Damaged membranes cannot be restored, so if water quality falls short of target, use probing and autopsy results to pick out and replace the damaged elements.

Finding the cause

The five hypotheses do not need investigating all at once. Strike them off starting with records that already exist. Temperature logs, the ORP and chemical consumption of the dechlorination system, and the cleaning log can be checked without stopping the unit, and normalisation needs only operating data. Probing can be done in operation but takes preparation, and pulling elements to weigh them or send them for autopsy comes after that.

The shape of the symptom is the first fork. A rise that flattens out after normalisation comes from operating conditions such as temperature, not the membrane. If salt passage rises with permeate flow also up, suspect oxidation by chlorine or cleaning chemicals first; with permeate flow unchanged, O-ring and seal leaks or mechanical damage to an element; with permeate flow down and differential pressure up, polarisation raised by scale and fouling (DuPont, 2021). Also check whether the date the rise began matches a cleaning, an element change or a day the chemical tank ran empty.

Next is location. Measure permeate conductivity from each pressure vessel; if only one is high, probe it to find the O-ring or damaged element. If the whole first stage is poor, look at oxidants in the feed or the colloids and iron that collect in the first stage; if the last stage worsened first, look at scale. Uniform deterioration across the unit points to temperature or to an event that reached the whole unit, such as a cleaning or disinfection.

If that still does not settle it, run a comparison. Do one cleaning matched to the deposit and see whether normalised salt passage recovers: the share that recovers is scale and fouling, and the share that remains is membrane damage. Replacing a suspect O-ring found by probing and then probing the same vessel again shows at once whether the leak was the cause. Oxidation and cleaning damage often cannot be fully told apart on site, so autopsying one element and analysing its membrane surface is the final check.

The hypotheses can overlap. Units that scale and foul often are cleaned often, and every cleaning is another chance for chemicals and heat to damage the membrane. High summer water temperature raises salt passage in its own right while also making scale easier to form. In such cases, remove the deposit first, read the remaining rise from normalised data, and then look for that share in damage and leaks, because the membrane's own change cannot be measured properly while a deposit remains.

Limits and cautions

Chlorine exposure tolerance, cleaning pH and temperature limits, maximum operating temperature and the triggers for cleaning differ by membrane and element type, so numbers follow the membrane manufacturer's data. Confirming oxidation or mechanical damage is work for a laboratory that autopsies elements, and where permeate serves strict water quality requirements such as pharmaceutical or semiconductor processes, do not keep supplying it on floor judgement alone; get the quality engineer to confirm.

Safety matters too. For sodium bisulfite, cleaning acids and alkalis, and sodium hypochlorite, follow each product's safety data sheet, the SDS, for protective equipment and ventilation, and keep acid and sodium hypochlorite from mixing. Before opening a pressure vessel end cap or fitting probing equipment, stop and lock out the high-pressure pump and confirm the pressure is released, and probe during operation only with the proper fitting and procedure.

Sources

  1. Antony, A., Low, J. H., Gray, S., Childress, A. E., Le-Clech, P., & Leslie, G. (2011). Scale formation and control in high pressure membrane water treatment systems: A review. Journal of Membrane Science, 383(1–2), 1–16. https://doi.org/10.1016/j.memsci.2011.08.054
  2. ASTM International. (2019). ASTM D4516-19a, Standard practice for standardizing reverse osmosis performance data. https://store.astm.org/d4516-19a.html
  3. ASTM International. (2023). ASTM D3923-23, Standard practices for detecting leaks in reverse osmosis and nanofiltration devices. https://store.astm.org/d3923-23.html
  4. DuPont Water Solutions. (2021). FilmTec reverse osmosis membranes technical manual (Form No. 45-D01504-en, Rev. 8).
  5. Ettori, A., Gaudichet-Maurin, E., Schrotter, J.-C., Aimar, P., & Causserand, C. (2011). Permeability and chemical analysis of aromatic polyamide based membranes exposed to sodium hypochlorite. Journal of Membrane Science, 375(1–2), 220–230. https://doi.org/10.1016/j.memsci.2011.03.044
  6. Gabelich, C. J., Frankin, J. C., Gerringer, F. W., Ishida, K. P., & Suffet, I. H. (2005). Enhanced oxidation of polyamide membranes using monochloramine and ferrous iron. Journal of Membrane Science, 258(1–2), 64–70. https://doi.org/10.1016/j.memsci.2005.02.034
  7. Gohil, J. M., & Suresh, A. K. (2017). Chlorine attack on reverse osmosis membranes: Mechanisms and mitigation strategies. Journal of Membrane Science, 541, 108–126. https://doi.org/10.1016/j.memsci.2017.06.092
  8. Hoek, E. M. V., & Elimelech, M. (2003). Cake-enhanced concentration polarization: A new fouling mechanism for salt-rejecting membranes. Environmental Science & Technology, 37(24), 5581–5588. https://doi.org/10.1021/es0262636
  9. Jin, X., Jawor, A., Kim, S., & Hoek, E. M. V. (2009). Effects of feed water temperature on separation performance and organic fouling of brackish water RO membranes. Desalination, 239(1–3), 346–359. https://doi.org/10.1016/j.desal.2008.03.026
  10. Sablani, S. S., Goosen, M. F. A., Al-Belushi, R., & Wilf, M. (2001). Concentration polarization in ultrafiltration and reverse osmosis: A critical review. Desalination, 141(3), 269–289. https://doi.org/10.1016/S0011-9164(01)85005-0
  11. Simon, A., McDonald, J. A., Khan, S. J., Price, W. E., & Nghiem, L. D. (2013). Effects of caustic cleaning on pore size of nanofiltration membranes and their rejection of trace organic chemicals. Journal of Membrane Science, 447, 153–162. https://doi.org/10.1016/j.memsci.2013.07.013
  12. Wijmans, J. G., & Baker, R. W. (1995). The solution-diffusion model: A review. Journal of Membrane Science, 107(1–2), 1–21. https://doi.org/10.1016/0376-7388(95)00102-I

Product and site consultation

Leave your company, site and the product groups in use. Our engineer will get in touch to go through your site conditions and concerns. Materials, equipment, operating conditions and downstream steps show what should change and what can stay. If nothing needs to change, we will say so.

Contact us
After you contact us
  1. 01
    Site setup

    We confirm process conditions and needs first.

  2. 02
    Spec design

    We set the product spec and selection criteria.

  3. 03
    Comparison

    We compare matching candidates and propose.

  4. 04
    Tailored supply

    We supply on time and manage the stock.

  5. 05
    Site check

    We visit, check conditions of use and record.

  6. 06
    Use management

    We track use and change cycles to catch issues.

  7. 07
    Regular analysis

    We analyze the records and send a yearly report.